Multistate values
Object
name
Object ID
Description
Values
Writeable
CclVlvPos
Mod
Multistate
value, 1
Manual/Auto
cool
output
1 = Off
2 = Manual
output
3 = Automatic
output
Yes
FanSpdMod
Multistate
value, 2
Fan mode select
1 = Off
2 = Manual
speed 1
3 = Manual
speed 2
4 = Manual
speed 3
5 = Auto
Yes
AppNr
Multistate
value, 3
Control
application
2 = 2-pipe
system
3 = 4-pipe
system
4 = 2-pipe
system with
electric heater
Yes
ChoverMod
Multistate
value, 4
Manual/Auto
change-over
1 = Heating
2 = Cooling
3 = Auto
Yes