Communication
Communication objects
8
30
| 52
A6V11917618_en--_b
Object
name
Object ID
Description
Values
Writeable
Chover
Status
Binary value, 7
Indicates changeover
status from both
digital and analog
input
Active /
inactive
No
Not used
Binary value, 8
-
-
-
Shdown
State
Binary value, 9
Places the unit in
'OFF' mode and
prevents it from being
activated again, unless
this value is first set to
'0'.
Active /
inactive
Yes
ShdownSet
Binary value, 10
Places the unit in
'OFF' mode
Active /
inactive
Yes
-
Binary value, 11
-
-
-
LockSettings
Binary value, 12
Prevents parameter
menu access via
display
Active /
inactive
Yes
Loop
Object
name
Object ID
Description
Controller
Loop, 0
Controller PI information
Multistate inputs
Object
name
Object ID
Description
Values
Writeable
Not used
Multistate
input, 0
-
-
No
ROpMode
Multistate
input, 1
Current running
mode
1 = Off
2 =
Economy/Standb
y
3 = Not used
4 = Not used
5 = Comfort
No
HCSta
Multistate
input, 2
Current control
mode
1 = Off
2 = Heating
3 = Cooling
No
Fan3Spd
Multistate
input, 3
Current fan
speed
1 = Off
2 = Fan speed 1
3 = Fan speed 2
4 = Fan speed 3
No