8
A6V11917618_en
--_b
37 | 52
Parameter
Name
Factory setting
Range
P59
BACnet MS/TP, device id, the
4 lowest digits
Lowest 4 digits of
device ID, as per
device label
-
P60
BACnet MS/TP, device id, the
3 highest digits
Highest 3 digits of
device ID, as per
device label
-
P61
BACnet MS/TP, maximum
number of master units
127
0…127
P62
Baud rate
3 = 76800 bps
0 = 9600 bps
1 = 19200 bps
2 = 38400 bps
3 = 76800 bps
P63
Reset communication
parameters to factory settings
0
1 = reset com.
parameters
P64
Basic comfort setpoint
22 °C
5… 50 °C
P65
Lock buttons
7 = all active
0 = No active
buttons
1 = Only On/Off
button active
2 = Only
Up/Down buttons
active
3 = On/Off and
Up/Down buttons
active
4 = Only fan
button active
5 = On/Off and
fan button active
6 = Up/Down and
fan button active
7 = all active
P66
Lock manual fan speed setting
according to P25
0 = Disable
0 = Disable
1 = Enable
P67
DC fan: Switching point fan
10 %
0…100 %
P68
Maximum DC fan speed
100 %
0…100 %
P69
Fan start kick time
0 = OFF
0 (Off)…10
seconds
P70
Supply air max. limitation for
cascade control and heating
control
35 °C
30…50 °C
P71
Supply air min. limitation for
cascade control and heating
control
24 °C
20…30 °C
P72
Supply air max. limitation for
cascade control and cooling
control
24 °C
15…30 °C