Functions
Communication objects (RDG2..KN)
4
130 | 186
A6V11545892_en--_e
Object No. and name
Thermostat
Object No. and name
RDG
1 System time
4 Fault information
2 Date
5 Fault status (0 = No alarm / 1 = Alarm)
3 Time of day
8 Room operating mode: Preselection
6 Fault transmission (0 = Disable / 1 = Enable)
94 Room operating mode: Status (receive)
17 Room operating mode: Status
7 Room operating mode: Preselection (receive)
9 Room operating mode: Preselection Auto
18 Room operating mode: Comfort status
10 Room operating mode: Preselection Comfort
19 Room operating mode: Economy status
11 Room operating mode: Preselection Economy
20 Room operating mode: Protection status
12 Room operating mode: Preselection Protection
13 Room operating mode: Time switch
27 Room temp: Comfort setpoint abs (send)
14 Room operating mode: Time switch Comfort
28 Room temp: Current setpoint
15 Room operating mode: Time switch Economy
31 Setpoint heat set (send)
16 Room operating mode: Time switch Protection
32 Setpoint cool set (send)
34 Room temperature: Comfort setpoint rel (send)
21 Room temp: [P19] Economy heating setpoint
35 Extended comfort mode status
22 Room temp: [P20] Economy cooling setpoint
37 Built-in room temperature value
23 Room operating mode: Window contact (0 = Close / 1 = Open)
38 Frost alarm (0 = No alarm / 1 = Alarm)
24 Room operating mode: Presence detector (0 = NotOccupied /
1 = Occupied)
39 Heat alarm (0 = No alarm / 1 = Alarm)
25 Room temp: Comfort basic setpoint
40 X1: Temperature [°C]
26 Room temp: Comfort setpoint abs (receive)
41 X1: Digital (0 = Off /1 = On)
42 X2: Temperature [°C]
29 Setpoint heat set (receive)
43 X2: Digital (0 = Off /1 = On)
30 Setpoint cool set (receive)
44 U1: Temperature [°C]
33 Room temperature: Comfort setpoint rel (receive)
45 U1: Digital (0 = Off /1 = On)
36 External room temperature value
47 Heating/Cooling mode status (1 = Heating / 0 = Cooling) (send)
46 Heating/Cooling mode status (1 = Heating / 0 = Cooling) (receive)
51 Fan operation (0 = Auto / 1 = Manual)
48 Application mode
53 Fan output
49 Dew point alarm (0 = No alarm / 1 = Alarm)
57 Fan speed 1 (0 = Off / 1 = On)
50 Enable fan command value (0 = Disable / 1 = Enable)
58 Fan speed 2 (0 = Off / 1 = On)
59 Fan speed 3 (0 = Off / 1 = On)
52 Fan command value
61 Heating, control value continuous
54 Fan speed 1 (0 = Off / 1 = On)
62 Heating, control value continuous, seq 2
55 Fan speed 2 (0 = Off / 1 = On)
63 Cooling, control value continuous
56 Fan speed 3 (0 = Off / 1 = On)
64 Cooling, control value continuous, seq 2
60 Outside temperature
65 Heating, control value status (0 = Inactive / 1 = Active)
66 Heating, control value status seq 2 (0 = Inactive / 1 = Active)
76 Enable electric heater (0 = Disable / 1 = Enable)
67 Cooling, control value status (0 = Inactive / 1 = Active)
68 Cooling, control value status seq 2 (0 = Inactive / 1 = Active)
78 External room relative humidity value [% r.h.]
69 Heating or cooling, control value status
(0 = Inactive / 1 = Active)
79 Room rel. humidity: Setpoint high
70 Heating or cooling, control value status seq2
(0 = Inactive / 1 = Active)
106 Room rel. humidity setpoint high Eco
80 Room rel. humidity: Setpoint low
71 Heating or cooling, control value continuous
81 Reset the Energy efficiency status (Green leaf)
(0 = No action / 1 = Reset)
72 Heating or cooling, control value continuous seq 2
83 Enable or disable Leaf indication (0 = Disable / 1 = Enable)
73 Control dehumidification (0 = Inactive / 1 = Active)
84 Keypad: Lock fan speed
74 Control humidification (0 = Inactive / 1 = Active)
85 Keypad: Lock fan speed in “auto” mode
75 Hum. Control mode (inactive/hum/dehum)
86 Keypad: Lock the setpoint shift
87 Keypad: Lock the operating mode
77 Built-in room relative humidity value [%r.h.]
82 Energy efficiency status / Green Leaf (0 = Green / 1 = Red)
89 Room operating mode: Window contact (0=Close/1=Open)
88 Room operating mode: Presence detector
(0=NotOccupied/1=Occupied)
92 Room temp: Current heating setpoint (receive)
91 Room temp: Current heating setpoint (send)
93 Room temp: Current cooling setpoint (receive)
90 Room temp: Current cooling setpoint (send)
96 ChangeOverWater status (1=Heating/0=Cooling) (receive)
95 ChangeOverWater status (1=Heating/0=Cooling) (send)
97 Manual fan command value (send)
98 DC fan speed: [P359] Maximum speed heating
99 DC fan speed: [P360] Maximum speed cooling
101 External room air quality value
100 Built-in room air quality value
102 DC damper demand
103 On/Off damper demand
104 PICV heating maximal position
105 PICV cooling maximal position
Input communication object
Output communication object

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RDG20 KN Series and is the answer not in the manual?

Siemens RDG20 KN Series Specifications

General IconGeneral
BrandSiemens
ModelRDG20 KN Series
CategoryThermostat
LanguageEnglish

Related product manuals