Control parameters
4
142 | 186
A6V11545892_en--_e
Parameter
Name
Factory
setting
Range
RDG20..
RDG26..
Dependencies
Expert level
Control settings
P050
Heat P-band Xp
2 K
0.5…6 K
P001
P051
Switching differential heating
1 K
0.5…6 K
P001
P052
Cool P-band Xp
P053
Switching differential cooling
P054
Radiator P-band Xp/switching
differential
2 K
0.5…6 K
P055
10)
Dead zone Comfort mode
2 K
0.5…5 K
M
M
P258
P056
Setpoint differential
2 K
0.5…5 K
P057
1)
Integral action time Tn for heating
45 min
0...120 min
P201,
P203,
P204
P058
1)
Integral action time Tn for cooling
P059
2)
10)
H/C changeover switching point
cooling
16 °C (61 °F)
5 °C…P060-2 K (41 °F…P060-2 K)
M
M
P001,
P150,
P153,
P155,
P258
P060
2)
10)
H/C changeover switching point
heating
28 °C (82 °F)
P059+2 K…40 °C (P059+2 K…104 °F)
M
M
P001,
P150,
P153,
P155,
P258
P061
11)
Setpoint ΔT cooling
---
--- (0), 1...40 K
P150,
P153,
P155
P062
11)
Setpoint ΔT heating
---
--- (0), 1...40 K
P150,
P153,
P155
P063
Minimum supply air temperature
---
---, 0 °C…P064 (32 °F…P064)
P150,
P153,
P155
P064
Maximum supply air temperature
---
---, P063…50 °C (P063122 °F)
P150,
P153,
P155
Mode and setpoints
P100
10)
Protection heating setpoint
8 °C (46 °F)
--- (0), 5 °CP101; (41 °F…P101)
M
M
P258
P101
10)
Protection cooling setpoint
---
--- (0), P100…40 °C; (P100…104 °F)
M
M
P258
P102
3)
10)
Temporary Comfort mode
---
--- (0), 1...360 min
M
M
P002,
P005,
P258
P103
10)
Temporary Comfort setpoint
OFF
0 = Disabled (OFF)
1 = Enabled (ON)
2 = Enabled (ON), excluded Window contact
3 = Enabled (ON), excluded presence detector
(include hotel presence)
M
M
P258
P104
10)
Setpoint display (RDG2..KN)
1
1 = Absolute setpoints
2 = Relative setpoints
M
M
P010
P258
P109
13)
Outside damper frost protection
(RDG2..KN)
---
---; 2...14 °C (35.6...50 °F)
P450
P110
10)
Energy indicator (RDG2..KN)
1
OFF = Disabled
1 = Green and Red dimmed out
2 = Green dimmed out / Red fixed
3 = Green and Red fixed
M
M
P258
P111
10)
Energy indicator range (RDG2..KN)
2 K
0…10 K
M
M
P258