4.15.4 Expert level parameters with diagnostics and test
Parameter display depends on selected application and function. Parameter values
are only visible when the device is set as Manager (M), Subordinate (S) or both
identification (✓).
Switching differential heating
Switching differential cooling
Radiator P-band Xp/switching
differential
Integral action time Tn for heating
Integral action time Tn for cooling
H/C changeover switching point
cooling
5 °C…P060-2 K (41 °F…P060-2 K)
P001,
P150,
P153,
P155,
P258
H/C changeover switching point
heating
P059+2 K…40 °C (P059+2 K…104 °F)
P001,
P150,
P153,
P155,
P258
Minimum supply air temperature
---, 0 °C…P064 (32 °F…P064)
Maximum supply air temperature
---, P063…50 °C (P063…122 °F)
Protection heating setpoint
--- (0), 5 °C…P101; (41 °F…P101)
Protection cooling setpoint
--- (0), P100…40 °C; (P100…104 °F)
Temporary Comfort setpoint
0 = Disabled (OFF)
1 = Enabled (ON)
2 = Enabled (ON), excluded Window contact
3 = Enabled (ON), excluded presence detector
(include hotel presence)
Setpoint display (RDG2..KN)
1 = Absolute setpoints
2 = Relative setpoints
Outside damper frost protection
(RDG2..KN)
---; 2...14 °C (35.6...50 °F)
Energy indicator (RDG2..KN)
OFF = Disabled
1 = Green and Red dimmed out
2 = Green dimmed out / Red fixed
3 = Green and Red fixed
Energy indicator range (RDG2..KN)