Siemens RDG20 KN Series - Different Ways to Influence Operating Mode

Siemens RDG20 KN Series
186 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
Operating modes
4
30 | 186
A6V11545892_en--_e
Source
Description
Value of data point
"Cause"
Local
operation via
left button
Operating mode is not Auto
No time schedule via bus
Room operating mode
selector (preselection)
Local time schedule
Local schedule
Temporary Comfort extension is
active
Timer function
Window contact
Window contact
Presence detector
Presence detector
Bus command
Room op.
mode
(RDG2..KN)
"Window contact" sent via bus
Window contact
"Presence detector" sent via bus
Presence detector
Time schedule available via bus
local operating mode is set to
Auto
Time schedule sends Protection
mode via bus
operating mode cannot be
changed locally
Time switch
Priority
Description
Remark
Commissioning
In parameter setting mode, you can always
command an operating mode independent of all
other settings or interventions via bus and local
input.
Protection mode via
bus from time
schedule
(RDG2..KN)
Protection mode, sent by a time schedule, cannot
be overridden by the users.
Window contact
If the contact is closed, the operating mode
changes to Protection. This overrides the
operating mode on the thermostat.
"Window contact"
via bus (RDG2..KN)
"Window contact" sent via bus has the same effect
as the local window contact.
Note:
Only one input source must be used, either local
input X1/X2/U1or KNX bus.
Source for change of
operating mode
ACS
Priority of operating
mode interventions