Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E
HVAC Products Application examples 15.07.2002
8.4 Plant types RVA47.320 - no. 30
The plant type no. is identical with the number displayed on line 53.
Control of a single BMU or cascade control of up to four BMUs. System pump for
heating circuits connected to the RVA47.320.
No d.h.w. heating via the RVA47.320.
4
1
2
3
B10
B70
2379S30
T
yp
e of unit BMU 1 BMU 2 BMU 3 BMU 4
RVA47.320
Dis
p
la
y
of
p
lant t
yp
e
30
Heatin
g
curve
(
line 17
)
---
(
inactiv
)
or 2.5...40
Pump function Q1 (line 95)
2 (primary pump for HC only) or
3
(p
rim
a
r
y
pu
m
p
f
o
r H
C
a
n
d
d
.h.w.
)
Heat generation is released by the heat demand signal from a consumer:
LPB capable controllers signal the RVA47.320 their current heat demand directly
via LPB.
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.
When there is no heat demand signal from the consumers (no LPB capable controllers
connected and no possibility to use input H1), the controller itself can generate a
weather-compensated flow temperature (adjustment of heating curve with a valid
value).
L
N
Q1
F1
N1
Q3
B3
B9
B70
B70
M
L
N
2379A30
MB
LPB
MD
A6 / BMU
PPS
DB
B10
B
M
H1
B10
B
M
B9
BM
A6
BM
H1
For a detailed legend, refer to page 158.
Note
Hydraulic circuit
Important
Electrical connections
Legend

Table of Contents