Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E
HVAC Products Description of the heating engineer settings 15.07.2002
Decrease: Switching differential will become smaller
Pumps are switched on and off more often
Room temperature varies within a narrower band
Increase: Switching differential will become greater
Pumps are switched on and off less often
Room temperature varies within a wider band
With pump heating circuits, the amount of heat supplied is controlled by switching the
pumps on and off. This is accomplished with two-position control by means of the room
temperature's switching differential.
Room temperature acquisition requires a room unit.
OFF
ON
P
°C
TRx
TRw+SDR
2371D02
TRw
t
°C
2379Z19
ON
OFF
w
TRx
P
[]
Pump ON TRx = TRw
Pump OFF TRx = TRw + SDR
4.30 Minimum limitation of the flow temperature
setpoint
Prevents too low flow temperatures
Minimum and maximum limitation define the range within which the flow temperature
setpoint may vary.
Room temperature
control
Note
Functioning:
Switching differential
Benefit
Description
TRx Actual value of the room temperature
TRw Room
temperature setpoint
SDR Switching
differential of room temperature
P Pump (ON / OFF)
w
Setpoint
Switch-on point
Switch-off point
Legend
TRx Actual value of the room temperature
TRw Room temperature setpoint
SDR Switching differential of room
temperature
ON Switch-on point
OFF Switch-off point
t Time
P Pump