22/166
Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E
HVAC Products Handling 15.07.2002
2.5 Parameter settings for the heating engineer
Configuration and parameter settings to be made by the heating engineer.
Buttons Explanation Line
1
Press one of the line selection buttons.
This will take you first to the programming level
"Enduser”.
2
Press both line selection buttons for at least 3 seconds.
This will take you to the programming level "Heating
engineer”.
3
Press the line selection buttons to select the required
line.
The parameter list on the next 2 pages contains all
available lines.
• • •
4
Press the + or - button to set the required value.
The setting will be stored as soon as you leave the
programming mode or change to another line.
The parameter list on the next 2 pages contains all
settings that can be made.
5
You leave the programming level "Heating engineer" by
pressing one of the operating mode buttons.
Note:
If no button is pressed for about 8 minutes, the
controller will automatically return to the operating
mode selected last.
Contin.
display
Description
Setting