Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E
HVAC Products Handling 15.07.2002
2.1.4 Required cut-out
The controller’s mounting dimensions are 91 x 91 mm.
Due to the dimensions of the front, however, the standard spacing is 96 mm.
The mechanical mounting facility allows the controller to be fitted in front panels having
a thickness of 2 to 10 mm.
The mechanical mounting facility makes
it possible to arrange several controllers
in a row in one cut-out. In that case, it is
merely necessary to have a wider panel
cutout.
2379 Z15
2.1.5 Orientation
To avoid overtemperatures inside the
controller, the inclination may be no
more than 30° and there must be a
clearance of at least 10 mm on all sides
of the unit.
This allows the controller to emit the
heat generated during operation.
1
0
m
m
m
a
x
.
3
0
°
2
3
7
1
Z
1
6
1
0
m
m
Dimensions of cut-out
96
2...10
92
+0.8
-0
92
+0.8
-0
96
92
+0.8
-0
2371M02
188
96
Use of several
controllers