EasyManua.ls Logo

Siemens S7 Series - Page 15

Siemens S7 Series
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 Configuration and Project Engineering
Communication with S7 CPU via KNX Gateway
Entry ID: 109739689, V1.0, 06/2017
15
Siemens AG 2017 All rights reserved
No.
Action
Comment
3.
Use drag and drop to move the “UGW-micro”
from the hardware catalog to the “Devices &
networks” editor.
4.
Click “Not assigned”) for the UGW-micro and
select the interface of the S7-1200 CPU used
(“PLC_1.PROFINET…”).
5.
Set the following PROFINET IP address:
S7-1200 CPU: 192.168.0.1
UGW-micro: 192.168.0.2
6.
Double-click the UGW-micro to open the
UGW-micro device view.
7.
Open the hardware catalog and navigate to
the gateway’s input/output modules.
Equip the UGW-micro with the required
modules.
Change the I/Q addresses to the range
starting with 100.
8.
Create a PLC tag table, for example
“TagsUGW”, as shown in the figure on the
right.
9.
Create the watch table, for example
“WatchTableUGW”, to monitor and modify the
tags.
Note

Related product manuals