EasyManua.ls Logo

Siemens S7 Series - Operation of the Application Example; Monitoring and Modifying Tags Using the Watch Table

Siemens S7 Series
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 Operation of the Application Example
Communication with S7 CPU via KNX Gateway
Entry ID: 109739689, V1.0, 06/2017
33
Siemens AG 2017 All rights reserved
6 Operation of the Application Example
You can verify communication between the S7-1200 and the KNX devices using
the watch table in TIA Portal and the functions of the KNX devices.
Table 6-1: Monitoring and modifying tags using the watch table
No.
Action
Comment
1.
In STEP 7 (TIA Portal), open the
“WatchTableUGW” watch table.
2.
1. Click the “Monitor all” button.
2. Monitor the room temperature of the KNX
room control unit.
3.
Compare the room temperature from the
watch table with the display in the KNX room
control unit.
4.
On the KNX room control unit, navigate to the
“SET” function named “KNXS7” and set a
new value.
5.
In the watch table, monitor the value change of
the “readValInt” tag.
2

Related product manuals