Connecting up
4.5 Signaling contact
SCALANCE XP-200
Operating Instructions, 05/2016, C79000-G8976-C428-01
61
Signaling faults
The signaling of errors by the signaling contact is synchronized with the fault LED "F",
see section ""F" LED (Page 29)".
All errors that the fault LED "F" indicates (freely configurable) are also signaled by the
signaling contact.
If an internal fault occurs, the fault LED "F" lights up and the signaling contact opens.
If you connect a communications node to an unmonitored port or disconnect it, this does
not cause an error message.
The signaling contact remains open until one of the following events occurs:
The problem is eliminated.
The current status is entered in the fault mask as the new desired status.
Connecting the signaling contact
1. Connect the plug and socket. Make sure that they lock in place correctly.
2. Tighten the knurled screw (torque 1 Nm).