Configuration, displays and display elements   
7.5 LED display 
  SCALANCE X-300 
150  Operating Instructions, 02/2012, A5E01113043-12 
Meaning in display mode D 
 
LED  Color  Status  Meaning 
_  off  Power supply L1 / L2 is not monitored. If L1 / L2 falls below 17 V *
)
, the 
signaling contact does not respond. 
L1 / L2 
green  on  Power supply L1 / L2 is monitored. If L1 / L2 falls below 17 V *
)
, the 
signaling contact responds. 
-  off  Power supplies L1 and L2 are not monitored. If L1 or L2 falls below 17 
V, the signaling contact does not respond. 
orange  on  Power supply L1 or L2 is monitored. If L1 or L2 falls below 17 V, the 
signaling contact responds. 
L 
green  on  Power supplies L1 and L2 are monitored. If L1 and L2 fall below 17 V, 
the signaling contact responds. 
*
)
) The following applies to the X-300EEC: 
•  For devices with power supply unit 24 to 48 VDC: Limit voltage = 17 VDC 
•  For devices with a multiple range power supply unit 100 to 240 VAC / 60 to 250 VDC: 
Limit voltage = 46.5 VDC or 80 VAC 
 
 
 
Note 
Devices of the X-300EEC product group 
When using only one power supply unit 24 VDC and two 24 VDC power supplies, the LEDs 
"L1" and "L2" signal the existence of the power supply L1 and L2. 
When using two 24 VDC power supply units, the LEDs "L1" and "L2" signal the existence of 
the primary voltage and the secondary voltage for both power supply units. If the power 
supply is intact, a fault occurring on a power supply unit on the secondary side can be 
recognized.