3 Detailed checklist
Checklist
Article ID: 109745536, V2.0, 05/2022
10
© Siemens AG
2022 All rights reserved
You can use "SNMPv1/v2c/v3" in the SNMP section. Ideally, you would
completely disable SNMPv1/v2 and instead use the secure SNMPv3 variant.
Note
With SNMPv1/v2, data are transmitted over the wire in cleartext.
With SNMPv3, the client can neither write nor read without a valid logon. Data are
transmitted in encrypted form.
Tick the "SNMPv1/v2 Read-Only" checkbox to prevent changes to the device
configuration via unsecure "SNMP Set" requests.
Change the Community Strings for SNMPv1/v2.
Disable the "SINEMA Configuration Interface" option if the device is not
managed with TIA or SINEC NMS. This turns off the configuration interface for
these tools.
After commissioning, set the DCP server to "Read Only".
3.4 Use secure FTP
Menu path
You can find this information "System > Load&Save" for MSPS devices.
Note on X-200 and X-300 devices
The switches only support "TFTP".
Recommendations for MSPS devices
Do not use "TFTP". The MSPS devices now offer a secure alternative with "SFTP".
3.5 DHCP client
Menu path
You can find this information in the following paths:
With MSPS: "System > DHCP"
With X-200 and X-300: "Agent > Agent DHCP Configuration"
Recommendation
If using the DHCP client, disable "DHCP Client Configuration Request (Opt.66,
67)".
Otherwise, the DHCP server can potentially reconfigure the device.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SCALANCE and is the answer not in the manual?

Siemens SCALANCE Specifications

General IconGeneral
Product FamilySCALANCE
FunctionEthernet Switch
Temperature Range-40°C to +70°C (depending on model)
Protection ClassIP20, IP30 (depending on the model)
MountingDIN rail, wall mounting (depending on the model)
Power Supply24 V DC
Number of PortsVaries by model (e.g., 4, 8, 24 ports)
TypeManaged, Unmanaged
SubtypesX, W, M, S
CertificationsCE, ATEX, IECEx (depending on the model)
Network ProtocolsPROFINET, Ethernet

Related product manuals