Manual for installation of the Sensformer® Connectivity Device
© 2020 Siemens Energy Page 11
REQUIREMENT
Do not use the cables without ferrules! The ferrules must be
certified!
For more information, see the Installation
requirements chapter.
REQUIREMENT
The using cables on the power supply must be double insulated
and must have UL 94 V-1 flammability classification and VW-1
flame rating.
For more information, see the Installation
requirements chapter.
Size of conductor: 1.5 mm
2
.
Tightening torque: < 1Nm.
Cable: double insulated, UL 94 V-1 flammability classification and
VW-1 flame rating.
Ferrule: certified, 1.5 mm
2
conductor area with 16-18 mm overall
length and 8 mm pin length.
During the wiring make sure that the PE is break last. The PE cable
must be longer with 2-3 cm like the L an N cables. The diameter
of used PE cable must be 1.5mm
2
.