Manual for installation of the Sensformer® Connectivity Device
© 2020 Siemens Energy Page 21
4.4. Digital Inputs
Number of
digital inputs
2
Logic 1 levels
48 240 VAC (adjustable) 50/60 Hz
or 48-240 VDC (adjustable)
Terminal type
2 poles
Terminal isolation
AC 3 kV
Polarity
Independent
Input impedance
88 kOhm
Size of conductor
1.5 mm
2
Table 6 – Parameters of digital inputs
4.5. PT100 Inputs
Number of PT100 inputs
1
Terminal type
4-wire
Separation Class
Class III (SELV)
Terminal isolation
AC 3 kV
Measurement range
0 – 200 Ohms
Measuring current
1 mA
Size of conductor
1.5 mm
2
Table 7 - Parameters of PT100 input
4.6. RS485 (ModBus)
Number of RS485 inputs
1
Baud Rate
9600 (not configurable)
Stopbits
2 (not configurable)
Parity
none (not configurable)
Terminal type
3-wire
Separation Class
Class III (SELV)
Terminal isolation
AC 3 kV
Size of conductor
1.5 mm
2
Table 8 - Parameters of RS485 port
4.7. Ethernet
Number of Ethernet port
1
Terminal type
RJ-45
Speed
10Mbit / 100Mbit
Separation Class
Class III (SELV)
Table 9 - Parameters of ethernet port
NOTE
The unit is to be connected only to internal Ethernet networks
without exiting facility and being subjected to TNVs.
4.8. Stored data
Type of stored data
Number of data
Analog per channel
1440
Digital per channel
1440
PT100 input
1440
ModBus registers data
Sum 3000
Table 10 - Stored data