Manual for installation of the Sensformer® Connectivity Device 
 
  © 2020 Siemens Energy  Page 15 
 
3.1.  Analog sensors 
Analog channel parameters, like gain, offset, unit and type can be 
set on the “Settings” sheet of the graphical user interface (GUI). 
 
Figure 15- Analog sensors 
 
Measured values are calculated according the following formula: 
value = Ax + B 
where x is the measured value by the device, A is the gain and B 
is the offset. 
The “Unit” specifies the physical unit of the converted value. The 
setting  “Type” defines  the operation  mode  of the analog input 
channels: AC input with +-20mA or DC input with 4-20mA range. 
The operation mode can be set for each channel individually. 
 
 
3.2.  Digital sensors 
The  digital  threshold  value  sets  the  limit  of  the  logical  “1” 
between 48-240VDC and 48-240VAC. The AC and DC modes can 
be changed and the threshold value can be set for the two digital 
channels individually.  The  threshold value is  equal  to  the input 
voltage border: if  the input voltage smaller  than the threshold, 
the digital input value is “0”, otherwise it is “1”. 
 
Figure 16 - Digital sensors section of web GUI 
 
A  voltage  divider  and  an  optocoupler  are  used  to  convert  the 
incoming  voltage  to  a  measurable  scale.  The  input  voltage 
converted by a 12bit A/D converter.  
In  DC  mode,  the  Sensformer  Connectivity  Device  can  measure 
and count the high level impulses, if the impulse width less than 
200ms and  more than 5ms. If the impulse width is greater than 
200ms, then the impulse width will be “0”, but the level value will 
be “1”. 
The device will show the shortest of several impulses of different 
width, but will count all of them, for example: 
 
Figure 17 - Pulse(s) on the digital inputs I. 
 
In this case, the impulse count value will be “2”, the impulse width 
will be “30”, and the digital value will be “0”. 
 
The impulse width measure is  working only with  the  high level 
impulses! If the signal default value is high, and the impulse level 
is low, the impulse measure is not working! For example: 
 
Figure 18 - Pulse(s) on the digital inputs II. 
 
In this case, the digital value will be “1”, the pulse width will be 
“0”, and the pulse count also will be “0”. 
But, for example: 
 
Figure 19 - Pulse(s) on the digital inputs III. 
 
In this case, the digital value will be “1”, the pulse count will be 
“1”, and the pulse width will be “45”. 
In DC mode, the sampling time is 1ms.