The measurement value recorder is responsible for recording average values, min and max values.
The measured values recorder intervals are defined according to the averaging intervals setting.
Table 7-14 PQDIF/CSV File Interval (measured value recorder)
Set
averaging
interval
Recording
duration for
creating a PQDIF
file
Time at start of
recording of a
complete PQDIF/
CSV file
Start of recording (recorder start option)
30 s 1 h 00:00 h
01:00 h
02.00 h
....
22:00 h
23:00 h
- start at the next minute limit
- start at the next 10-minute limit
- immediate start
- start at the next hour limit
- start next day
1 min 2 h 00:00 h
02:00 h
04.00 h
....
20:00 h
22:00 h
10 min 2 h, 4 h, 6 h, 12 h
oder 24 h
15 min
30 min
1 h