EasyManuals Logo

Siemens SIMATIC EP200SP User Manual

Siemens SIMATIC EP200SP
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
Parameters/address space
4.2 Explanation of parameters
Digital output module DQ 8x24VDC/0.5A SNK BA (6ES7132-6BF61-0AA0)
16 Manual, 09/2017, A5E32855878-AB
4.2
Explanation of parameters
Diagnostics: No supply voltage L+
Enabling of the diagnostics for no or insufficient supply voltage L+.
Channel activated
Determines whether a channel is activated or deactivated.
Reaction to CPU STOP
Determines the behavior of the module in the event of a CPU STOP.
Potential group
A potential group consists of a group of directly adjacent I/O modules within an ET 200SP
station, which are supplied via a common supply voltage.
A potential group begins with a light-colored BaseUnit through which the required voltage is
supplied for all modules of the potential group. The light-colored BaseUnit interrupts the
three self-assembling voltage buses P1, P2 and AUX to the left neighbor.
All additional I/O modules of this potential group are plugged into dark-colored BaseUnits.
You take the potential of the self-assembling voltage buses P1, P2 and AUX from the left
neighbor.
A potential group ends with the dark-colored BaseUnit, which follows a light-colored
BaseUnit or server module in the station configuration.
See also
ET 200SP distributed I/O system
(http://support.automation.siemens.com/WW/view/en/58649293
)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC EP200SP and is the answer not in the manual?

Siemens SIMATIC EP200SP Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC EP200SP
CategoryControl Unit
LanguageEnglish

Related product manuals