Interrupts, error messages, diagnostics and system alarms
5.3 Alarms
IM 157-1 DP (6ES7157-1AA00-0AB0)
36 Equipment Manual, 08/2021, A5E32100641-AE
5.3.3 Station statuses 1 to 3
The following tables show station status 1 to 3 and provide an overview of the status of a DP
slave.
Structure of station status 1 (byte 0)
Table 5- 5 Structure of station status 1 (byte 0)
Bit
Meaning
Cause/Solution
0
1: The DP slave is not responding to the DP
master.
Correct PROFIBUS address set on the DP
slave?
Bus connector connected?
Is the DP slave connected to the voltage
supply?
RS485 repeater properly configured?
1
1: The DP slave is not yet ready to exchange
data.
Wait; the DP slave is currently starting
up.
2
1: The configuration data transferred from
the DP master to the DP slave does not
match the DP slave configuration.
Has the correct station type or the cor-
rect DP slave configuration been entered
in the configuration software?
3
1: External diagnostics is available. (Group
diagnostics display)
Evaluate the ID-specific diagnostics, the
module status, and/or the channel diag-
nostics. As soon as all errors have been
eliminated, bit 3 is reset. The bit is set
again when there is a new diagnostics
alarm in the bytes of the aforemen-
tioned diagnostics.
4
1: The requested function is not supported
by the DP slave (e.g. changing the PROFIBUS
address using software).
Check the configuration.
5
1: The DP master cannot interpret the re-
sponse of the DP slave.
Check the bus configuration.
6 1: The DP slave type does not match the
software configuration.
Has the correct station type been en-
tered in the configuration software?
7
1: Parameters have been assigned to the DP
slave by a different DP master (not the one
that currently has access to the DP slave).
The bit is always 1, for example, if you
access the DP slave with the program-
ming device or another DP master.
The PROFIBUS address of the DP master
that assigned parameters to the DP slave
is located in the "Master PROFIBUS ad-
dress" diagnostics byte.