Product overview
2.3 Properties
CPU 1510SP-1 PN (6ES7510-1DJ01-0AB0)
Equipment Manual, 05/2021, A5E03506268-AD
15
Properties
The CPU 1510SP-1 PN has the following technical properties:
Communication:
Interfaces
The CPU 1510SP-1 PN has a PROFINET interface (X1 P3) with an integrated 3-port
switch. Port 1 and port 2 are located on the optionally pluggable BusAdapter. Port 3 is
integrated in the housing of the CPU. The CPU supports the BusAdapters BA 2xRJ45
and BA 2xFC. You connect the PROFINET IO to the CPU via the BusAdapter.
In addition to PROFINET basic functionality, the interface also supports PROFINET IO RT
(real-time) and IRT (isochronous real-time). PROFINET IO communication or real-time
settings can be configured. The basic functionality of PROFINET supports HMI
communication, communication with the configuration system, communication with a
higher-level network (backbone, router, Internet) and communication with another
machine or automation cell.
Port 1 and port 2 can also be used as ring ports for the configuration of redundant ring
structures in Ethernet.
Note
The CPU is delivered without a BusAdapter. You can find the article numbers of the
supported BusAdapters in the "Accessories/spare parts" section of the ET
200SP
distributed automation system
(http://support.automation.siemens.com/WW/view/en/58649293) system manual.
The CM DP is optionally available with a PROFIBUS interface (X2). You can find
additional information about this expansion module in the manual Communication
module CM DP (http://support.automation.siemens.com/WW/view/en/90156526).
You can find information about connecting the PROFINET IO BusAdapter to the CPU as
well as connecting the optional PROFIBUS interface to the interface module in the
system manual ET 200SP distributed I/O system
(http://support.automation.siemens.com/WW/view/en/58649293).
OPC UA
With OPC UA, data is exchanged via an open and vendor-neutral communication
protocol. The CPU, as OPC UA server, can communicate with OPC UA clients such as
HMI panels, SCADA systems, etc.
Integrated Web server:
A Web server is integrated in the CPU. You can read out the following information with
the Web server:
Start page with general CPU information
Identification information
Contents of the diagnostics buffer
Query of module states
Firmware update
Alarms (without acknowledgment option)

Other manuals for Siemens simatic et200sp

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens simatic et200sp and is the answer not in the manual?

Siemens simatic et200sp Specifications

General IconGeneral
CategoryI/O Systems
Power Supply24 V DC
Protection RatingIP20
Number of ModulesUp to 64 modules
MountingDIN Rail
Communication ProtocolsPROFINET, PROFIBUS
Storage Temperature-40 °C to +70 °C
Digital InputsYes (depending on module)
Digital OutputsYes (depending on module)
Analog InputsYes (depending on module)
Analog OutputsYes (depending on module)
ModularityModular
Relative Humidity5 to 95% (non-condensing)
WeightVaries by configuration
System TypeDistributed I/O