B-4
Operator Panel OP3
Edition 11/99
ActionCauseMessage
$ 040 No response from PLC
Cable defective or not plugged in
Check physical connection
$ 041 Temporary driver error Restart PC
Re-send configuration
$ 044 MPI transfer error
$ 045 No connection to PLC No. x
(message with variable )
$ 100 Invalid RAM contents
$ 104 Download mode aborted by operator in-
put (OP3 or ProTool/Lite)
$ 119 Automatic start by OP3
Password list is not necessarily deleted
$ 202 Error on reading date Re-enter date
(return OP3 for repair)
$ 203 Error on reading time Re-enter time
(return OP3 for repair)
$ 311 Flag x does not exist on PLC Modify configuration (variable)
$ 316
$ 317
Current password level too low for requi-
red operator input
Login at higher password
level
$ 318 Login attempted with invalid password
$ 319 While editing the password, a password
was entered which already exists
$ 320
$ 321
Superuser level cannot be modified; pass-
word invalid
Enter password before defining level
$ 322 Password too short Password must have at least 3 characters
$ 324 The screen number you entered does not
exist
$ 340 When the status function is being execu-
ted on the PU, you cannot operate the
OP3
$ 401 Entered value does not match display for-
mat
$ 402 Operating error on STATUS VAR or
FORCE VAR screen
$ 403 Incorrect time input
S
y
stem Messa
g
es

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC HMI OP3 and is the answer not in the manual?

Siemens SIMATIC HMI OP3 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC HMI OP3
CategoryControl Panel
LanguageEnglish

Related product manuals