EasyManua.ls Logo

Siemens SIMATIC HMI TP 070 - Page 61

Siemens SIMATIC HMI TP 070
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Data
A-3
TP 070 Equipment Manual
Release 03/00
Ambient conditions
Location
Max. permissible angle of inclination
without external ventilation
vertical
"35°
Max. permissible ambient temperature
Operation
STN display
Vertical installation
Installation angled from the
perpendicular to max. 35°
0...+50 °C
0...+40 °C
Shipping, storage –20...+60 °C
Relative humidity
Operation
Shipping, storage
20...85%, no condensation
5...90%, no condensation
Shock loading
Operation
Shipping, storage
15 g/11 msec
25 g/6 msec
Vibration
Operation 0.035 mm (10 – 58 Hz)
1 g (58 – 500 Hz)
Shipping, storage 3.5 mm (5 – 8,5 Hz)
1 g (8.5 – 500 Hz)
Barometric pressure
Operation
Shipping, storage
706 to1030 hPa
581 to 1030 hPa