Certification
6.1.9RoHS
6.1.9 RoHS
This device is declared by Siemens Canada Ltd. to meet the requirements of the
following RoHS (Restriction of Hazardous Substances) directives for the restricted use
of certain hazardous substances in electrical and electronic equipment:
• EU RoHS Directives (EU) 2011/65 and (EU) 2015/863
European Directive for Restriction of Hazardous Substances
• China RoHS (relating to SJ/T 11364)
Management Methods for the Restriction of the Use of Hazardous Substances in
Electrical and Electronic Products
Declarations of conformity for each directive are available online via Siemens
Industry Online Support [https://support.industry.siemens.com/].
6.1.10 Other Approvals
This device meets the requirements of the following additional standards:
• IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications
Networking Devices in Electric Power Substations
• IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
• IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General
Requirements
• NEMA TS-2
Traffic Controller Assemblies with NTCIP Requirements
6.2 EMC and Environmental Type Tests
The RUGGEDCOM RS900 has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Tests
Test Description Test Levels Severity
Levels
Enclosure
Contact
± 8 kV 4IEC
61000-4-2
ESD
Enclosure Air ± 15 kV 4
IEC
61000-4-3
Radiated RFI Enclosure
Ports
20 V/m
IEC
61000-4-4
Burst (Fast Transient) Signal Ports ± 4 kV @ 2.5 kHz x
34
RUGGEDCOM RS900
Equipment Manual, 11/2023, C79000-G8976-1024-16