Certification
6.2EMC and Environmental Type Tests
Test Description Test Levels Severity
Levels
DC Power
Ports
± 4 kV 4
AC Power
Ports
± 4 kV 4
Earth
Ground Ports
± 4 kV 4
Signal Ports ± 4 kV Line-to-Ground
± 2 kV
4
DC Power
Ports
± 2 kV Line-to-Ground
± 1 kV Line-to-Line
3
IEC
61000-4-5
Surge
AC Power
Ports
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
4
Signal Ports 10 V 3
DC Power
Ports
10 V 3
AC Power
Ports
10 V 3
IEC
61000-4-6
Induced (Conducted) RFI
Earth
Ground Ports
10 V 3
IEC
61000-4-8
Magnetic Field Enclosure
Ports
40 A/m Continuous
1000 A/m for 1 s
IEC
61000-4-11
Voltage Dips and Interrupts AC Power
Ports
100% for 5 Periods
100% for 50 Periods
Signal Ports 2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
3
DC Power
Ports
2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
3
IEC
61000-4-12
Damped Oscillatory
AC Power
Ports
2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
3
Signal Ports 30 V Continuous
300 V for 1 s
4IEC
61000-4-16
Mains Frequency Voltage
DC Power
Ports
30 V Continuous
300 V for 1 s
4
IEC
61000-4-17
Ripple on DC Power Supply DC Power
Ports
10% 3
IEC
61000-4-29
Voltage Dips and Interrupts DC Power
Ports
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
RUGGEDCOM RS900
Equipment Manual, 11/2023, C79000-G8976-1024-16
35

Table of Contents

Other manuals for Siemens SIMATIC NET RUGGEDCOM RS900

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET RUGGEDCOM RS900 and is the answer not in the manual?

Siemens SIMATIC NET RUGGEDCOM RS900 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC NET RUGGEDCOM RS900
CategorySwitch
LanguageEnglish

Related product manuals