Certification
6.2EMC and Environmental Type Tests
Test Description Test Levels
AC Power Ports ± 4 kV @ 2.5 kHz, 5 kHz
Earth Ground Ports ± 4 kV
Signal Ports 2.5 kV Common
Mode @ 1 MHz
IEEE 1613 Oscillatory
DC Power Ports 2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
Signal Ports 5 kV (Failsafe Relay)
DC Power Ports 5 kV
IEEE 1613 HV Impulse
AC Power Ports 5 kV
Signal Ports 2 kV (Failsafe Relay)
DC Power Ports 2.8 kVDC or 2 kV
IEEE 1613 Dielectric
Strength
AC Power Ports 2 kV
IEEE 1613.1
IEC 61000-4-10
Damped
Oscillating
Magnetic
Field
Enclosure Ports 100 A/m for 1 s (100
kHz and 1 MHz)
Environmental Type Tests
Test Description Test Levels Severity Levels
Cold Temperature Test Ad -40 °C (-40
°F), 16 Hours
IEC 60068-2-1
Cold Storage Test Ab -40 °C (-40
°F), 16 Hours
Dry Heat Test Bd 85 °C (185
°F), 16 Hours
IEC 60068-2-2
Dry Heat Storage Test Bd 85 °C (185
°F), 16 Hours
IEC 60068-2-30 Humidity (Damp
Heat, Cyclic)
Test Dd 95% (Non-
Condensing),
55 °C (131
°F), 6 Cycles
IEC 60068-2-14 Change of
Temperature
Test Nb 5 Cycles @
-40 to 85 °C
(-40 to 185 °F)
IEC 60068-2-78 Humidity (Damp
Heat, Cyclic)
Test Cab 10 Days @ 55 °C
(131 °F), 6 Cycles
IEC 60255-21-1 Vibration 2 g @ 10 to 150 Hz Class 2
IEC 60255-21-2 Shock 30 g @ 11 ms Class 2
IEC 60255-21-2 Bump 10 g @ 16 ms Class 1
IEC 60255-21-3 Seismic Method A Class 2
IEC 60529 Ingress Protection IP4x
IEEE 1613
IEC 60068-2-31
Free Fall 100 mm (3.9 in)
RUGGEDCOM RST916C
Installation Manual, 04/2023, C79000-G8976-1490-07
41