4-4
Connecting TM I/O to PCS 7
C79000-G8076-C710-04
call SIMATIC Manager
open the current project
select the M7 program of the FM456-4
PLC ³ Manage M7 target system ...
select the medium ”Memory Card”
select the ”Install OS” tab
select ³ install ”M7 RMOS32”(confirm all prompts)
å the Memory Card is formatted, M7-SYS will be installed.
PLC ³ Manage M7 target system ...
select the medium ”Memory Card”
select the ”Programs” tab
select ³ install ”Blocks” (when prompted to write batch files to
\etc\inittab, confirm with ”Yes”)
å the HW configuration, configured connections and configuration
DBs are now copied.
Since the system software is not visible in SIMATIC Manager when the op-
tional package M7-ProC/C++ has not been installed, the system SW and all
its components must be copied to Memory Card, using Windows Explorer:
select the catalog \Siemens\Step7\S7libs\Pcs7_tm\hrs\P0000002\
copy the file TM_EA_S7.EXE to mc:\romdir
create a new catalog mc:\S7auto on Memory Card
copy the file TM_EA_S7.BAT to mc:\S7auto
copy the file BGRLISTE.TYP to mc:\romdir
edit the file mc:\etc\inittab:
At the end of the file in block ”Init 2 - not synchronized user ...”
enter the line:
2 \s7auto\tm_ea_s7.bat
M7-SYS
Blocks
System SW
Confi
g
uration

Table of Contents

Other manuals for Siemens SIMATIC PCS 7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC PCS 7 and is the answer not in the manual?

Siemens SIMATIC PCS 7 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC PCS 7
CategoryControl Systems
LanguageEnglish

Related product manuals