4-7
Connecting TM I/O to PCS 7
C79000-G8076-C710-04
If you specifically assign all modules to the 100-ms cycle, cycle conflict is
switched off, but the respective cycle might be overloaded in this operation.
When you choose such an ”Overload configuration” (e.g. to obtain swift and
conflict-free processing as far as possible), you must nevertheless take into
account that the processing time for this cycle is increased accordingly.
4.4 Extended module configuration
In addition to transparent SIMATIC interface modules (see Table 4-3 in
Chapter 4.7), you must also configure the subordinate I/O modules. Do so by
opening DB2 in the block container of FM456-4, using the block editor.
After you select ”Data view” iin the ”View” menu, you can see the following
figure, for example:
Table 4-2
Address
Name Type Start value Actual
value
Comment
0 . 0 NR0001.BGNR INT -1 114 Module no. of the TM module
2 . 0 NR0001.Kanal INT 0 8 Channel number (Offset)
4 . 0 NR0001.S5_Typ STRING [ 4 ] ’ ’ ’DE2’ S5 Module type
10 . 0 NR0002.BGNR INT -1 114 Module no. of the TM module
12 . 0 NR0002.Kanal INT 0 0 Channel number (Offset)
14 . 0 NR0002.S5_Typ STRING [ 4 ] ’ ’ ’DA1’ S5 Module type
20 . 0 NR0003.BGNR INT -1 114 Module no. of the TM module
22 . 0 NR0003.Kanal INT 0 1 Channel number (Offset)
24 . 0 NR0003.S5_Typ STRING [ 4 ] ’ ’ ’DA1’ S5 Module type
30 . 0 NR0004.BGNR INT -1 114 Module no. of the TM module
32 . 0 NR0004.Kanal INT 0 2 Channel number (Offset)
34 . 0 NR0004.S5_Typ STRING [ 4 ] ’ ’ ’DA1’ S5 Module type
40 . 0 NR0005.BGNR INT -1 114 Module no. of the TM module
42 . 0 NR0005.Kanal INT 0 3 Channel number (Offset)
44 . 0 NR0005.S5_Typ STRING [ 4 ] ’ ’ ’DA1’ S5 Module type
50 . 0 NR0006.BGNR INT -1 -1 Module no. of the TM module
52 . 0 NR0006.Kanal INT 0 0 Channel number (Offset)
54 . 0 NR0006.S5_Typ STRING [ 4 ] ’ ’ ’ ’ S5 Module type
60 . 0 : : : : :
62 . 0 : : : : :
64 . 0 : : : : :
The ”Name” column shows you the consecutive number of the configured S5
module.
Select the ”Actual value” column. Enter the slot number of the TELEPERM
module configured in DB1 in the ”Module no. of the TM module” (refer to
Table 4-1 in Chapter 4.3) row.
In the ”Channel number” row, enter the byte address. Configure the S5 mo-
dule ID in the ”S5 module type” row.
Confi
g
uration