4-5
Connecting TM I/O to PCS 7
C79000-G8076-C710-04
4.3 Example of how to use the block editor to configure I/O
The sample below shows the basic steps for configuration.
The entries are verified on startup of the FM456-4.
Possible inconsistencies are displayed and stored in the diagnostic s buffer of
FM456-4.
To configure TELEPERM I/O modules, open SIMATIC-Manager, then open
the DB 1 you have generat ed during installation per double-click in the block
container of FM456-4. Next, select ”Data view” from the ”View” menu. This
opens, for example, the following view:
Table 4-1
Address
Name Type Start value Actual value Comment
0.0 BGNR000.BG_Typ STRING [ 16 ] ’’ ’6DS1601-8BA Module type (6DS1...)
18 . 0 BGNR000.Zyklus INT 0 8 TPM478 processing cycle
20 . 0 BGNR001.BG_Typ STRING [ 16 ] ’’ ’6DS1603-8RR’ Module type (6DS1...)
38 . 0 BGNR001.Zyklus INT 0 8 TPM478 processing cycle
40 . 0 BGNR002.BG_Typ STRING [ 16 ] ’’ ’6DS1701-8AA Module type (6DS1...)
58 . 0 BGNR002.Zyklus INT 0 8 TPM478 processing cycle
60 . 0 BGNR003.BG_Typ STRING [ 16 ] ’’ ’6DS1702-8RR’ Module type (6DS1...)
78 . 0 BGNR003.Zyklus INT 0 8 TPM478 processing cycle
80 . 0 BGNR004.BG_Typ STRING [ 16 ] ’’ ’6DS1607-8AB’ Module type (6DS1...)
98 . 0 BGNR004.Zyklus INT 0 8 TPM478 processing cycle
100 . 0 BGNR005.BG_Typ STRING [ 16 ] ’’ 6DS1401 -8CA Module type (6DS1...)
118 . 0 BGNR005.Zyklus INT 0 8 TPM478 processing cycle
120 . 0 BGNR006.BG_Typ STRING [ 16 ] ’’ 6DS1603 -8RR’ Module type (6DS1...)
138 . 0 BGNR006.Zyklus INT 0 8 TPM478 processing cycle
140 . 0 BGNR007.BG_Typ STRING [ 16 ] ’’ ’’ Module type (6DS1...)
158 . 0 BGNR007.Zyklus INT 0 8 TPM478 processing cycle
: : : : : :
: : : : : :
: : : : : :
1238 . 0 BGNR061.Zyklus INT 0 0 TPM478 processing cycle
1240 . 0 BGNR100.BG_Typ STRING [ 16 ] ’’ ’6DS1603-8RR Module type (6DS1...)
1258 . 0 BGNR100.Zyklus INT 0 8 TPM478 processing cycle
1260 . 0 BGNR101.BG_Typ STRING [ 16 ] ’’ ’6DS1605-8BA Module type (6DS1...)
1278 . 0 BGNR101.Zyklus INT 0 8 TPM478 processing cycle
: : : : : :
: : : : : :
: : : : : :
1558 . 0 BGNR113.Zyklus INT 0 0 TPM478 processing cycle
1520 . 0 BGNR114.BG_Typ STRING [ 16 ] ’’ ’6DS1310-8AA Module type (6DS1...)
1538 . 0 BGNR114.Zyklus INT 0 8 TPM478 processing cycle
1540 . 0 BGNR115.BG_Typ STRING [ 16 ] ’’ ’’ Module type (6DS1...)
: : : : : :
: : : : : :
: : : : : :
Conf
i
g
u
r
a
t
i
on

Table of Contents

Other manuals for Siemens SIMATIC PCS 7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC PCS 7 and is the answer not in the manual?

Siemens SIMATIC PCS 7 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC PCS 7
CategoryControl Systems
LanguageEnglish

Related product manuals