4-13
Connecting TM I/O to PCS 7
C79000-G8076-C710-04
4.7 Substitute config u ration for 6DS1504-8AA / 6DS1505-8AA
4.7.1 Rules for PCS7/TM
The signals ”Enable Manual” (EM) and ”Enable Automatic” (EA) only exist
once in 6DS1504-8AA and 6DS1505-8AA. It is there fore required to switch
over in the same way in all drivers defined for a module. Otherwise, the
function is not ensured. In any case, full SW control can only be reached if
the status is not established by ha rdware forcing of the ”Enable Manual” si-
gnal (connector X2) (refer to the operating instructions on the 6DS1504-8AA
or 6DS1505-8AA module).
4.7.2 Substitute configuration for PCS7/TM
For PCS7/TM the result is the following confi guration of 6DS1504-8AA /
6DS1505-8AA :
Configuration rules
MNO=21; Example of MNO
BG_Typ=6DS1310-8AA; Substitute configuration-always enter
1310-8AA!
.Cycle=....; The cycle must always be faster than
the fastest cycle of the EG driver blocks
assigned to this module.
.Kanal=8
.S5_Typ=DE2
Kanal=0; Only ent er if operating EG driver type 0, 1 or 2 with
CNO=0.
.S5_Typ=DA1; Only enter if operating EG driver type 0, 1 or 2 wit h
CNO=0..
.Kanal=1; Only ent er if operating EG driver type 0, 1/KNR=1 or
type 2/KNR=0.
.S5_Typ=DA1; Only enter if operating EG driver type 0, 1/KNR=1 or
type 2/KNR=0.
Kanal=2; Only ent er if operating EG driver type 0, 1 or 2 with
CNO=2.
.S5_Typ=DA1; Only enter if operating EG driver type 0, 1 or 2 wit h
CNO=2.
.Kanal=3; Only ent er if operating EG driver type 0, 1/KNR=3 or
type 2/CNO=2.
.S5_Typ=DA1; Only enter if operating EG driver type 0, 1/KNR=3 or
type 2/CNO=2.
The remaining entries are only for 6DS1505-8AA:
.Kanal=4; Only ent er if operating EG driver type 0, 1 or 2 with
CNO=4.
DB1
DB2
Conf