Technical specifications
A.1 General technical specifications
S7-1200 Functional Safety Manual
138 Manual, 02/2015, A5E03470344-AA
A.1.9
Protection class
Protection Class II according to EN 61131-2:
S7-1200 is open equipment and must be enclosed in additional protection as described in
Section 4.1.2: "Guidelines for installing S7-1200 Fail-Safe devices" (Page 80).
S7-1200 systems including AC power supply or relays which can be connected to AC
voltage achieve Class II when installed in a suitable enclosure.
S7-1200 systems including only connections to SELV / PELV achieve Class III when
installed in a suitable enclosure.
You do not require a protective conductor. The S7-1200 has no protective ground
connection.
A.1.10
Degree of protection
IP20 Mechanical Protection, EN 60529
Protects against finger contact with high voltage as tested by standard probe. External
protection required for dust, dirt, water and foreign objects of < 12.5mm in diameter.