Technical specifications
A.3 Fail-Safe signal module (SM) technical specifications
S7-1200 Functional Safety Manual
184 Manual, 02/2015, A5E03470344-AA
A.3.4
SM 1226 F-DQ 2 x Relay
A.3.4.1
Properties
Article number
6ES7 226-6RA32-0XB0
Properties
The SM 1226 F-DQ 2 x Relay has the following features:
Two relay outputs (each output switches two circuits)
5 A output current
Rated load voltage 24 VDC or 24 VAC to 230 VAC
Module fault display (DIAG; green and red LED)
Status display for each output (green LED)
Fault display for each output (red LED)
Safety class SIL3 attainable
Assignable diagnostics
Refer to "Fault diagnostics" (Page 119) for a description of LED and diagnostic message
functions.
A.3.4.2
User data space
The SM 1226 F-DQ 2 x Relay user data space is 2 process value output bits followed by 2
quality bits.
This is the bit structure for an F-RLY module configured with input start address 8:
Terminal
Process value
Quality bit
F-DQ a.0
Q8.0
I8.0
F-DQ a.1
Q8.1
I8.1