Software section
3.2 Creating the program
S7-1500
Getting Started, 05/2014, A5E03981761-AC
61
Procedure
1. Open the "Filling" data block and the "Main" program block.
2. Enable the "Monitoring on/off" function for the "Main" program block.
3. In the "Main" program block, open the shortcut menu of the "'FILLING'
FillingLevel_CMYK_C" I/O in the 3 network with a right-click and select "Modify > Modify
operand".
4. Enter a new value and click "OK".
5. Enable the "Download without reinitialization" function and the "Monitor all" function in the
"Filling" data block.
6. Create a new parameter named "DT_Loc-T_Last_Filling" and select "Date_And_Time" as
the data type.