5.5.4.2 Failure of one redundancy connection and the primary CPU in S7-1500H
Introduction
The following failure scenario describes the effects of a defect in a redundancy connection
and the primary CPU in S7-1500H using a PROFINET ring as example. In this failure scenario,
the time between the failure of the redundancy connection failure and of the primary CPU is
>55ms.
Failure scenario
① Primary CPU → failed (2nd failure in sequence of events)
② Backup CPU
③ One fiber-optic cable (redundancy connection) → interrupted (1st failure in sequence of
events)
④ IO device ET 200SP
⑤ IO device ET 200MP
⑥ PROFINET cable (PROFINET ring)
Figure 5-42Failure of one redundancy connection and the primary CPU
Sequence of events
1.
One of the two redundancy connections is interrupted.
2.
Availability is restricted. The redundant system will remain in the RUN-Redundant system
state.