7.5 Connecting the supply voltage
Introduction
The supply voltage is supplied over a 4-pin connector at the front of or bottom of the R/H-
CPU.
Connection for supply voltage (X80)
The connections of the 4-pole connector have the following meaning:
/
/0
0
+24VDC of the supply voltage (current limited to 10A)
Ground of the supply voltage (current limited to 10A)
Ground of the supply voltage for loop-through
+24VDC of the supply voltage for loop-through
Spring opener (one spring opener per terminal)
Figure 7-3Connection for supply voltage
The cable connector enables you to loop the supply voltage uninterrupted, even when it is
unplugged.
Requirements
Only wire the cable connector when the supply voltage is turned off.
Follow the wiring rules (Page 174).
Tool-free connection of cables: multi-wire (stranded), with end sleeve or ultrasonic compressed
To connect a wire without tools, follow these steps:
1.
Strip 8 to 11 mm of the wires.
2.
Seal or crimp the wire with end sleeves.
3.
Insert the cable into the push-in terminal as far as it will go.
4.
Push the wired connector into the socket of the CPU.
Tools required
3 to 3.5mm slotted-head screwdriver
176
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD
Wiring
7.5 Connecting the supply voltage