EasyManua.ls Logo

Siemens Simatic S7-1500H - Replacing Defective Redundancy Connections; Replacing Two Defective PROFINET Cables with S7-1500 R

Siemens Simatic S7-1500H
393 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13.1.3 Replacing defective redundancy connections
Introduction
This section describes the following replacement scenarios:
S7-1500R:
Replace defective PROFINET cable with S7-1500R.
The PROFINET ring has been interrupted at any given point. You can find additional
information in the section Replacing defective PROFINET cables (Page 326).
Replace two defective PROFINET cables with S7-1500R.
The PROFINET ring has been interrupted at two points.
S7-1500H:
Replace a defective redundancy connection with S7-1500H.
A fiber-optic cable has been interrupted.
Replace defective synchronization module with S7-1500H.
Replace two defective redundancy connections with S7-1500H.
Both fiber-optic cables have been interrupted.
Evaluating the diagnostics buffer
Detailed diagnostics information is provided in the diagnostics buffer of the R/H-CPU. The
entries are particularly useful in the replacement scenarios for the redundancy connections:
S7-1500R: They contain information on whether one PROFINET cable or both PROFINET
cables have been interrupted or a port of an R-CPU is defective.
S7-1500H: You can access information on whether a fiber-optic cable has been
interrupted or the synchronization module is defective (with additional module
diagnostics).
13.1.3.1 Replacing two defective PROFINET cables with S7-1500R
Initial situation: Failure of two PROFINET cables, one after the other
Two PROFINET cables in the PROFINET ring have been interrupted one after the other at two
points (>1500ms apart).
The S7-1500R redundant system is in the RUN-Solo system state.
Requirement
Read the information in the section Checking before replacing components (Page 319).
323
Maintenance
13.1 Replacing components of the S7-1500R/H redundant system
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD