OB72 (CPU redundancy error)
In addition to the OBs of the S7‑1500 CPU, you can also use OB72 (CPU redundancy error).
The operating system of each CPU of an R/H-system calls up the CPU redundancy error OB
(OB72) when one of the following events occurs:
Loss of redundancy due to a CPU failure
Loss of redundancy due to a CPU transition to STOP mode (triggered by the user or the
system)
Up to firmware version V2.8:
The R/H system has entered the RUN-Redundant system state.
As of firmware version V2.9:
The R/H-system has entered RUN-Redundant system state and the synchronization of the
two R/H-CPUs is possible redundantly.
The R/H-system has entered RUN-Redundant system state, but the synchronization of the
two R/H-CPUs is not possible redundantly.
The R/H-system is still in RUN-Redundant system state and the synchronization of the two
R/H-CPUs is possible redundantly now or again.
The R/H-system is still in RUN-Redundant system state, but the synchronization of the two
R/H-CPUs is no longer possible redundantly.
NOTE
An R/H-system with non-redundant synchronization may not tolerate any further failures. In
this case, you need to check and possibly repair the PROFINET ring (R-system) or the fiber-
optic cables (H-system) immediately.
OB 70 (IO redundancy error)
As of firmware version V3.0, OB 70 (I/O redundancy error) is available for the diagnostics of
R1 and S2 devices in S7-1500H systems.
The operating system of the CPUs calls OB70 if a redundancy loss or a redundancy return
occurs in the system state RUN-Redundant at a redundant R1/S2 device. Loss of redundancy
means that one AR of two ARs of an R1/S2 device fails. Redundancy return means that the
second AR of an R1/S2 device returns.
For example, the loss of redundancy is caused by one of the following events:
Failure of an S2 device due to voltage failure
Failure of one of two interface modules of the R1 device
Line interruption on one side of the R1 or S2 device
OB 70 is only called in the system state RUN-Redundant. When the H-system leaves the
system state RUN-Redundant, OB 72 (CPU redundancy error) is called.
STEP7 online help
You can find additional information on instructions and blocks in the STEP7 online help.
216
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD
Basics of program execution
9.1 Programming the S7-1500R/H