Synchronization of primary and backup CPU ensures rapid switchover between CPUs in the
event of a failure of the primary CPU. If the primary CPU fails, the backup CPU takes over
control of the process as the new primary CPU.
The synchronization of the H-CPUs does not affect the bandwidth on the PROFINET.
Reference
Additional information and configuration variants (e.g. combined topology) of the S7-1500H
redundant system can be found in the section Specific configuration variants of the S7-1500H
redundant system (Page 80).
Differences between S7-1500R and S7-1500H
Table 4-1S7-1500R and S7-1500H system differences
S7-1500R S7-1500H
CPU 1513R‑1PN
CPU 1515R‑2PN
CPU 1517H‑3PN
CPU 1518HF-4 PN
Performance Transfer rate of 100Mbps (for synchronization
and communication)
Data work-memory:
CPU 1513R-1 PN: max. 2.5MB
CPU 1515R-2 PN: max. 4.5MB
Code work-memory:
CPU 1513R-1 PN: max. 600KB
CPU 1515R-2 PN: max. 1MB
Significantly greater performance than
S7‑1500R due to:
Separate redundancy connections over
fiber-optic cable
High computing power
transfer rate of 1Gbps (for synchronization)
Data work-memory:
CPU 1517H-3 PN: max. 8MB
CPU 1518HF-4 PN: max. 60MB
Code work-memory:
CPU 1517H-3 PN: max. 2MB
CPU 1518HF-4 PN: max. 9MB
Hardware The CPUs are identical in design with the
respective S7‑1500 standard versions.
Synchronization of the CPUs takes place over
the PROFINET ring.
When you use PROFINET devices with more
than two ports (e.g. switch) in the PROFINET
ring of an R-system, then H-Sync Forwarding is
mandatory for these devices.
H-Syncforwarding is recommended for all
devices in the PROFINET ring if you are using
PROFINET devices with only 2 ports in the
PROFINET ring of an R-system.
Part of the bandwidth on the PROFINET cable is
required for synchronization of the CPUs. Less
bandwidth is therefore available for
PROFINETIO communication.
The CPUs each have 2 optical interfaces.
The synchronization of the CPUs works inde
pendently from the PROFINET network via
optical fiber.
The full bandwidth of the PROFINET cable is
available for PROFINET IO communication.
Range Distance between the two R-CPUs:
Max. 100m without media converter
Several kilometers with media converter
(depends on the media converter used)
Distance between the two H-CPUs:
Maximum of 40km (depends on the syn
chronization modules used)
32
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD
System overview
4.1 What is the S7-1500R/H redundant system?