Operating Modes, parameters and commands
7.3 Count modes
FM 350-1 Counter module
112 Manual, 05/2011, A5E03648639-01
Status of the Outputs and Status Bits
The status of the two outputs is indicated by the green LEDs and the corresponding status
bits in the DB.
Table 7- 20 Output DO0
Comparison
condition
Enable bit
CTRL_DO0
Status bit
STS_COMP1
Status bit
STS_CMP1/
Output DO0
LED DO0
0 0 0 Out Not fulfilled
1 0 0 Out
0 1 0 Out Fulfilled
1 1 1 Is lit
Table 7- 21 Output DO1
Comparison
condition
Enable bit
CTRL_DO1
Status bit
STS_COMP2
Status bit
STS_CMP2/
Output DO1
LED DO1
0 0 0 Out Not fulfilled
1 0 0 Out
0 1 0 Out Fulfilled
1 1 1 Is lit
Status bits STS_CMP1 and STS_CMP2 indicate the current status of outputs DO0 and DO1.
If enabled, they are set by CTRL_DO0 and CTRL_DO1 if a comparison condition is fulfilled
and are reset if the condition is not fulfilled.
Status bits STS_COMP1 and STS_COMP2 are set by CTRL_DO0 and CTRL_DO1 if a
comparison condition is fulfilled, regardless of whether they are enabled, and remain set until
you acknowledge the status bits with RES_ZERO.