Wiring the FM 350-1
3.2 Wiring front connectors
FM 350-1 Counter module
Manual, 05/2011, A5E03648639-01
31
3.2 Wiring front connectors
Cables
Here are some rules for you to observe when selecting cables:
The cables for digital inputs DI Start, DI Stop and DI Set must be shielded.
The cable for the counter signals must be shielded.
You must apply the shields of the counter signal cables both at the pulse encoder and in
the immediate vicinity of the module via the shield attachment, for example.
The following cables of the incremental 5 V encoder have to be twisted in pairs.
A and /A
B and /B
N and /N
$
$
%
%
1
1
'&9
0








6KLHOGRQ
VKLHOGVXSSRUW
6KLHOGRQ
KRXVLQJ
)URQWFRQQHFWRU
7ZLVWHGFDEOHV
Figure 3-2 Details Regarding the Connection of an Incremental 5V Encoder