EasyManua.ls Logo

Siemens SIMATIC S7-300 FM 350-1 - Encoders Which Can be Connected

Siemens SIMATIC S7-300 FM 350-1
198 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Encoder signals and their evaluation
8.1 Encoders which can be connected
FM 350-1 Counter module
160 Manual, 05/2011, A5E03648639-01
8.1 Encoders which can be connected
Introduction
The counter module can process rectangular count signals which were generated by
incremental encoders or pulse generators.
Incremental encoders scan a barcode to generate rectangular electrical pulses. They differ in
terms of pulse amplitude and number of signals.
Pulse generators such as light barriers or proximity switches (BEROs) return only a
rectangular signal at a specific amplitude.
Connecting different encoders
The counter module supports different encoders which return pulses for the count signals.
The table shows these encoders and the corresponding signals.
Table 8- 1 Encoders which can be connected
Encoders Signal
5-V incremental encoder Differential signals A and /A, B and /B, N and /N
24-V incremental encoder A*, B* and N*
24-V pulse encoder 24-V with directional signal
24-V proximity switch 24 V without directional signal

Table of Contents