Programming the FM 350-1
5.7 Programming FM 350-1 without FCs
FM 350-1 Counter module
62 Manual, 05/2011, A5E03648639-01
5.7.3 Control interface for measuring modes
Control interface for measuring modes
Parameter LOAD_VAL (bytes 0 to 3) has two different meanings:
● You set bit L_PREPAR to define the LOAD_VAL parameter as a low limit.
● You set bit C_DOPARA bit in byte 0 to define the reaction at output DO0.
Table 5- 16 Control interface for measuring modes (outputs)
Offset to the start
address
Parameter Assignment
Bytes 0 to 3 LOAD_VAL Load low limit with bit L_PREPAR
Define reaction of DO0 at bit C_DOPARA
Bits 2 to 7 Bit 1 Bit 0 Reaction of output DO0
Irrelevant 0 0 No comparison
Irrelevant 0 1 Out of limits
Irrelevant 1 0 Below the low limit
Irrelevant 1 1 Above the high limit
Byte 0
Byte 1 Reserve = 0
Byte 2 Reserve = 0
Byte 3
LOAD_VAL
Reserve = 0
Bytes 4 to 7 CMP_V1 High limit; load with bit T_CMP_V1
Bytes 8 to 9 CMP_V2 Update time; load with bit: T_CMP_V2
Bytes 10 to 11 – –
Byte 12 –
NEUSTQ
–
–
OT_ERR_A
–
–
–
Bit 7: Reserve = 0
Bit 6: Restart acknowledgement
Bit 5: Reserve = 0
Bit 4: Reserve = 0
Bit 3: Operator error acknowledgement
Bit 2: Reserve = 0
Bit 1: Reserve = 0
Bit 0: Reserve = 0
Byte 13 –
–
–
–
SW_GATE
GATE_STP
–
–
Bit 7: Reserve = 0
Bit 6: Reserve = 0
Bit 5: Reserve = 0
Bit 4: Reserve = 0
Bit 3: SW gate control bit
Bit 2: General gate stop
Bit 1: –
Bit 0: –