Wiring the FM 350-1
3.3 Module status after power on
FM 350-1 Counter module
34 Manual, 05/2011, A5E03648639-01
3.3 Module status after power on
Default setting
Module status after power on and before any parameters were transferred:
No gate - i.e., the gate is open
Counter inputs with default setting for 5 V differential signals, track B not inverted; single
evaluation (refer to the section Signal Evaluation (Page 166))
0 to +32 bit counting range
Counter status zero
Set counter with signal at input DI Set (and zero mark) locked
Input delay for digital inputs DI Start, DI Stop and DI Set typically 1 µs
(max. frequency: 200 kHz, minimum pulse width: 2.5 µs)
Input delay at 24 V counter inputs: typically 1 µs
(max. frequency: 200 kHz, minimum pulse width: 2.5 µs)
Outputs DO0 and DO1 disabled
Pulse duration = 0
No hardware interrupts set
"Continuous count" mode is set
Status messages are updated