Operating Modes, parameters and commands
7.4 Measuring modes
FM 350-1 Counter module
144 Manual, 05/2011, A5E03648639-01
Limit Monitoring
The following value ranges are permitted for limit value monitoring:
Table 7- 36 Speed capture: Value Ranges for Limit Monitoring
Lower limit n
u
Upper limit n
o
0 to 24 999 999 *10
-3
/min n
u
+1 to 25 000 000 *10
-3
/min
Possible Measuring Ranges with Error Information (for Number of Pulses per Encoder Revolution
= 60)
Table 7- 37 Speed Capture: Measuring Ranges and Errors
Speed n
min
Absolute error Speed n
min
Absolute error
1 /min ±0.04 /min 1 000 /min ±0.21 /min
10 /min ±0.04 /min 10 000 /min ±1.82 /min
100 /min ±0.05 /min 25 000 /min ±4.5 /min
Function of the DI Start and DI Stop Digital Inputs
You can choose between the following functions for the digital inputs:
Level-controlled hardware gate
Edge-controlled hardware gate
See Chapter Command: Open and close gate (Page 149))
Function of Digital Output DO0
You can choose between the following functions for digital output DO0:
No comparison (no switching by limit value monitoring)
Measured value outside limits
Measured value under lower limit
Measured value above upper limit
(See the section Behavior of the Digital Outputs (Page 153))