Programming the FM 350-1
5.2 The function FC CNT_CTL1 (FC 2)
FM 350-1 Counter module
46 Manual, 05/2011, A5E03648639-01
DB address Parameters Meaning
x = irrelevant
Bit 7 Bit 6 Bit 5 Bit 4 Reaction of output DO1
x 0 0 0 Inactive
x 0 0 1 Active from comparison value to overflow
x 0 1 0 Active from comparison value to underflow
x 0 1 1 Active on reaching the comparison value for pulse
duration (up/down)
x 1 0 0 Active on reaching the comparison value for pulse
duration (up)
x 1 0 1 Active on reaching the comparison value for pulse
duration (down)
x 1 1 0 Switch to comparison values
x = irrelevant
15.0 Hysteresis (range of values 0 to 255)
16.0 Pulse duration (value range 0 to 250)
17.0
Reserve = 0
18.0 CMP_V1 Comparison value 1; load with function parameter: T_CMP_V1
22.0 CMP_V2 Comparison value 2; load with function parameter: T_CMP_V2
Parameters for Transferring Values in the DB (Measuring Modes)
The following table shows the range of the DB in which you transfer the LOAD_VAL,
CMP_V1 and CMP_V2 parameters.
The LOAD_VAL parameter (bytes 14 to 17) has two meanings:
● If you set function parameter L_PREPAR, LOAD_VAL is interpreted as a low limit
● If you set function parameter C_DOPARA, Byte 14 is used to define the behavior of
Output DO0.
You must not set the L_DIRECT parameter for a measuring mode.