Cycle and reaction times
5.4 Calculating method for calculating the cycle/response time
CPU 31xC and CPU 31x, Technical Data
5-18 Manual, 01/2006 Edition, A5E00105475-06
5.4 5.4 Calculating method for calculating the cycle/response time
Introduction
This section gives you an overview of how to calculate the cycle/response time.
Cycle time
1. Determine the user program runtime with the help of the
Instruction list
.
2. Multiply the calculated value by the CPU-specific factor from the table
Extension of user
program processing time
.
3. Calculate and add the process image transfer time. Corresponding guide values are
found in table
Data for calculating process image transfer time
.
4. Add the processing time at the scan cycle checkpoint. Corresponding guide values are
found in the table
Operating system processing time at the scan cycle checkpoint
.
5. Include the extensions as a result of testing and commissioning functions as well as
cyclical PROFINET interconnections in your calculation. These values are found in the
table
Cycle time extension due to testing and commissioning functions.
The final result is
the cycle time.
Extension of the cycle time as a result of interrupts and communication load
100 / (100 – configured communication load in %)
1. Multiply the cycle time by the factor as in the formula above.
2. Calculate the runtime of interrupt processing program sections with the help of the
instruction list. Add the corresponding value from the table below
.
3. Multiply both values by the CPU-specific extension factor of the user program processing
time.
4. Add the value of the interrupt-processing program sequences to the theoretical cycle
time, multiplied by the number of triggering (or expected) interrupt events within the cycle
time. The result is an approximation of the physical cycle time. Note down the result.
See also
Cycle extension through Component Based Automation (CBA) (Page 5-10)

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals