Cycle and reaction times
5.6 Sample calculations
CPU 31xC and CPU 31x, Technical Data
Manual, 01/2006 Edition, A5E00105475-06
5-25
Response times plus I/O delay:
Case 1: An output channel of the digital output module is set when a signal is received
at the digital input. The result is a response time of:
Response time = 42 ms + 4.8 ms = 46.8 ms.
Case 2: An analog value is fetched, and an analog value is output. The result is a
response time of:
Longest response time = 42 ms + 176 ms + 3.3 ms = 221.3 ms.
5.6.3 Example of interrupt response time calculation
Design
You have assembled an S7-300, consisting of one CPU 314C-2 and four digital modules in
the CPU rack. One of the digital input modules is an SM 321; DI 16 x 24 VDC; with
process/diagnostic interrupt function.
You have enabled only the process interrupt in your CPU and SM parameter configuration.
You decided not to use time-controlled processing, diagnostics or error handling. You have
configured a 20% communication load on the cycle.
You have configured a delay of 0.5 ms for the inputs of the DI module.
No activities are required at the scan cycle checkpoint.
Calculation
In this example, the process interrupt response time is based on following time factors:
Process interrupt response time of CPU 314C-2: approx. 0,7 ms
Extension by communication according to the formula:
200 μs + 1000 μs x 20 % = 400 μs = 0.4 ms
Process interrupt response time of SM 321; DI 16 x 24 VDC:
Internal interrupt preparation time: 0.25 ms
Input delay: 0.5 ms
Neither PROFIBUS DP, nor PROFINET IO are being used, so you do not have to make
allowances for any DP cycle times on PROFIBUS DP or for PROFINET IO update times.
The process interrupt response time is equivalent to the sum of the listed time factors:
Process interrupt response time = 0.7 ms + 0.4 ms + 0.25 ms + 0.5 ms = approx. 1.85 ms.
This calculated process interrupt response time expires between the time a signal is
received at the digital input and the call of the first instruction in OB40.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals