EasyManuals Logo

Siemens SIMATIC S7-300 Module data Technical Data Manual

Siemens SIMATIC S7-300 Module data
252 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #99 background imageLoading...
Page #99 background image
Cycle and reaction times
5.3 Response time
CPU 31xC and CPU 31x, Technical Data
Manual, 01/2006 Edition, A5E00105475-06
5-13
Tips and notes
The upper graphic already includes the use of uniform values for the transfer frequency of all
interconnections to a partner.
The performance can drop by up to 50 % if the values are distributed to different
frequency levels.
The use of data structures and arrays in an interconnection instead of many single
interconnections with simple data structures increases the performance.
5.3 5.3 Response time
5.3.1 Overview
Definition of response time
The response time is the time between the detection of an input signal and the change of a
linked output signal.
Fluctuation width
The physical response time lies between the shortest and the longest response time. You
must always reckon with the longest response time when configuring your system.
The shortest and longest response times are shown below, to give you an idea of the
fluctuation width of the response time.
Factors
The response time depends on the cycle time and following factors:
Delay of the inputs and outputs of signal modules or integrated I/O.
Additional update times for PROFINET IO
additional DP cycle times on PROFIBUS DP
Execution in the user program
Reference
The delay times are located in the specifications of the signal modules (
Module data
Reference Manual).
Update times for PROFINET IO
If you configured your PROFINET IO system in STEP 7, STEP 7 calculates the update time
for PROFINET IO. You can then view the PROFINET IO update times on your PG.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals