EasyManuals Logo

Siemens SIMATIC S7-300 Module data Technical Data Manual

Siemens SIMATIC S7-300 Module data
252 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #76 background imageLoading...
Page #76 background image
Memory concept
4.1 Memory areas and retentivity
CPU 31xC and CPU 31x, Technical Data
4-8 Manual, 01/2006 Edition, A5E00105475-06
4.1.5 Properties of the SIMATIC Micro Memory Card (MMC)
The SIMATIC Micro Memory Card (MMC) as memory module for the CPU
The memory module used on your CPU is a SIMATIC Micro Memory Card. You can use
MMCs as load memory or as a portable storage medium.
Note
The CPU requires the SIMATIC Micro Memory Card for operation.
The following data are stored on the SIMATIC Micro Memory Card.
User programs (all blocks)
Archives and recipes
Configuration data (STEP 7 projects)
Data for operating system update and backup
Note
You can either store user and configuration data or the operating system on the SIMATIC
Micro Memory Card.
Properties of the SIMATIC Micro Memory Card (MMC)
The SIMATIC Micro Memory Card ensures maintenance-free and retentive operation of
these CPUs.
Caution
Data on a SIMATIC Micro Memory Card can be corrupted if you remove the card while it is
being accessed by a write operation. In this case, you may have to delete the SIMATIC
Micro Memory Card on your PG, or format the card in the CPU. Never remove a SIMATIC
Micro Memory Card in RUN mode. Always remove it when power is off, or when the CPU is
in STOP state, and when the PG is not writing to the card. When the CPU is in STOP mode
and you cannot not determine whether or not a PG is writing to the card (e.g. load/delete
block), disconnect the communication lines.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)